High-Current Tests

The term high-current tests summarizes types of tests which may need several kilo amps to be performed.

Tests are performed with a test voltage according to the appropriate standard, for example 115% of the rated voltage of the test object.


A requirement given by the standards is that devices and power distribution systems have to fulfill their specified functions safely at these extreme short-circuit currents. The expanding energy density of the energy grid makes it necessary to provide extreme test currents far beyond 100,000 Amps for tests. I²PS has one of the world's most powerful testing systems.

Generator

Tests with extreme short-circuit currents are used to examine the behavior that switchgear and assemblies are being exposed to at the limits of their technical and physical capacity. The results achieved with these tests are extremely important and serve to reassure project developers, installers, and owners that a switchgear device or a power distribution system will be able to meet all applicable requirements resulting from extreme failure or fault scenarios. An extensive control system makes it possible to precisely control all test procedures and to monitor system components.
This ensures that a few seconds after completion of the test, he testing system is able to provide all the information required for a competent and comprehensive evaluation of the test results. Other special measuring techniques from the Test Laboratory Bonn, such as high-speed video, laser vibrometers, and x-ray analyses, can be used as well.

Relevant Standards:

IEC/EN 60947, IEC EN 61439-1 und 2, IEC / EN 60269, additional standards in conformity with UL, CSA und SABS

DUTs:

Low-voltage switchgear, low-voltage switchgear systems, low-voltage fuses, miniature circuit-breakers, variable frequency drives, soft starters, etc.

Prüfzelle

An overloadtest is used to determine the tripping values for overload and short-circuit releases. The limits of the tripping values for the overload test, specified by the technical committees of the standards, are tested at various ambient temperatures. The following parameters provide information regarding our testing capability:

 

  • Overload currents up to 12,000 A
  • Short-circuit capacity up to 25,000 A
  • Temperature characteristics of –25 °C to +60 °C
  • Harmonic up to 700 A / 1,500 Hz

Relevant Standards:

IEC/EN 60947, UL 508, UL 508C, UL 845, UL 1008, CAN/CSA C22.2 No60947-5-1

DUTs:

All devices that have a corresponding protective function, such as circuit-breakers, overload relays, fuses, etc.

Schaltschrank in der Erwärmungsprüfung

Temperature rise tests on electrical equipment and switchgear assemblies are used to determine the thermal designof contacts and conductors, as well as the insulating material components of the current carrying parts. In addition, these tests are used to verify that the permitted temperature values are within the limits as required by national and international standards. In order to be able to analyze long-time temperature rise tests for the verification of suitability, I²PS GmbH's measuring system has been specifically expanded to make it possible to record, analyze, and document physical variables such as forces and voltage drops as well. Since temperature rise tests cannot be conducted with extra-low voltage for all test objects (e.g., frequency converters and soft starters), there is a wide variety of load circuits and motors available as loads for this purpose.

Relevant Standards:

IEC / EN 60947, IEC / EN 61439, IEC / EN 60269, UL489, UL508

DUTs:

Switchgear, distribution systems, components, terminals, etc.

Schaltschrank in der Störlichtbogen

An arc fault is a short-circuit that can occur due to a fault between live parts with different potentials and/or between live parts and bodies and can be the type of a high-current arc discharge (ionized gas plasma with a temperature of approx. 10,000 °C or higher – normally air). These tests are used to verify safety for operating personnel and the public.

 

Relevant Standards:

IEC/TR 61641 respectively DIN EN IEC 60439-2 addendum 2

DUTs:

Switchgear systems, switchgear combinations, low-voltage devices, medium-voltage devices

Kontakte der Transformatoren

Devices such as electrical assemblies are protected from overcurrents by upstream protection devices. With our high-current test systems, we can determine trip values or potentially check if further to requirements from relevant product standards are being met. To determine the tripping current the test object is operated with its rated current. Then the current is increased until tripping occurs. Alternatively, the test object is loaded with a constant current, in which case the tripping characteristic is determined based on the time it takes for the device to trip.

Relevant Standards:

IEC / EN 60947, IEC / EN 60898, IEC / EN 60269

DUTs:

Circuit-breakers, relays, fuses, etc.

Transformatoren

The purpose of conducting an impulse withstand current test on current-carrying equipment such as switchgear or power distribution systems is to determine the mechanical stability of this equipment when subjected to large dynamic electromagnetic forces caused by the high currents.

 

Relevant Standards:

IEC / EN 61439, IEC / EN 60947-series

DUTs:

Switchgear systems, distribution systems, busbar systems, etc.

Transformatoren

Short-time withstand current testing is used to verify that a switchgear device or a distribution system is able to carry a short-circuit current for a specific time without being damaged.

 

Relevant Standards:

IEC / EN 60947-Reihe, IEC / EN 61439-series

DUTs:

Switchgear, distribution systems, busbar systems

 


The power for the relevant test is generated by three surge generator systems. The largest of these systems has a generator output of 298 MVA and, with a short-circuit power of 207 MVA, is one of the most powerful short-circuit testing systems in all of Europe. The following testing options are available for DC and within a frequency range of 16 2/3 Hz to 60 Hz:

 

AC-High Current Tests
Short circuit, Switching capacity 3phase, 50/60 Hz, 200 ms
Test Voltage Test Current
               240 V (60 Hz) 200 kA
   253 V 300 kA
   440 V 275 kA
               480 V (60 Hz) 200 kA
   525 V 250 kA
   550 V 200 kA
               600 V (60 Hz) 200 kA
  725 V 175 kA
              770 V (60 Hz) 160 kA
1100 V 100 kA
1500 V 85 kA
AC-Short time withstand current
3phase, 50 Hz
Test Voltage Test Current Current Flow Time
440 V 65 kA 3000 ms
525 V 80 kA 2000 ms
525 V 120 kA 1000 ms

 

 

 

 

 

DC-High Current Tests
Short circuit, Switching capacity 200ms
Test Voltage Test Current
262 V 40 kA
550 V 50 kA
630 V 60 kA
788 V 70 kA
1500 V 70 kA
1575 V 70 kA
DC-Short time withstand current
Test Voltage Test Current Current Flow Time
48 V-1500 V 20 kA 1000 ms

 

 

 

 

We use cookies

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.